Skip to product information
Dwyer Instruments CDT-2N4E | Carbon Dioxide/Temperature | Wall Mount | Universal current/voltage output | Pt1000 RTD Temperature Output | North American Housing - generaltechuae

Dwyer Instruments CDT-2N4E | Carbon Dioxide/Temperature | Wall Mount | Universal current/voltage output | Pt1000 RTD Temperature Output | North American Housing

Part Number : CDT-2N4E

The Dwyer CDT-2N4E is a wall-mount carbon dioxide and temperature transmitter designed for indoor environmental monitoring. It measures CO₂ from 0 to 2000 PPM and provides a Pt1000 Ω RTD temperature output, with a universal CO₂ output selectable between 4–20 mA, 0–5 VDC, and 0–10 VDC.

Genuine Dwyer Instruments stock · Free UAE-wide shipping

Part Number: CDT-2N4E

Request a quote in under a minute — call +971 6 5436933.

Product Overview

The Dwyer CDT-2N4E combines CO₂ and temperature measurement in a single wall-mounted transmitter, helping building and HVAC systems monitor indoor air conditions while reducing the number of devices required in occupied spaces.

The transmitter measures CO₂ concentrations from 0 to 2000 PPM and uses a Pt1000 Ω RTD for temperature measurement across 32 to 122°F (0 to 50°C). Its universal CO₂ output can be configured for 4–20 mA, 0–5 VDC, or 0–10 VDC, allowing integration with a wide range of building automation and HVAC control systems.

A single-beam, dual-wavelength NDIR sensor provides CO₂ measurement with a stated 15-year life expectancy. The sensor automatically corrects measurement against light-source aging effects, while digital barometric pressure adjustment and field calibration capability support accurate operation over time.

The CDT-2N4E features a North American wall-mount housing with an IP20 enclosure rating. Push buttons provide access to the transmitter's menu structure, while an internal DIP switch can lock the controls to help prevent unwanted changes. A backplate electrical connection simplifies installation.

With CO₂ and temperature measurement combined in one device, the CDT-2N4E is suited to applications such as demand-controlled ventilation, schools, offices, hospitals, and LEED-driven ventilation monitoring.

For applications requiring local visual indication, the CDT-2N4E-LCD provides the same transmitter configuration with an integral LCD display.

Key Benefits

  • Measures CO₂ from 0 to 2000 PPM
  • Combines CO₂ and temperature measurement in one wall-mount transmitter
  • Pt1000 Ω RTD temperature output
  • Universal CO₂ output: 4–20 mA, 0–5 VDC, or 0–10 VDC
  • Single-beam, dual-wavelength NDIR CO₂ sensor
  • 15-year sensor light-source life expectancy
  • Digital barometric pressure adjustment and field calibration capability
  • Lockable push-button menu access
  • North American wall-mount housing
  • Backplate electrical connection for installation
  • IP20 enclosure rating
  • Genuine Dwyer Instruments stock with free UAE-wide shipping

Who This Product Is Best For

The Dwyer CDT-2N4E is suitable for:

  • HVAC and building automation systems requiring CO₂ monitoring
  • Demand-controlled ventilation in schools, offices, and hospitals
  • Projects requiring CO₂ and temperature measurement from a single wall-mounted device
  • LEED-driven ventilation monitoring
  • Building operators monitoring indoor environmental conditions
  • Control systems requiring a selectable 4–20 mA, 0–5 VDC, or 0–10 VDC CO₂ signal

How to Specify & Commission It

  1. Mount the CDT-2N4E wall housing and use the backplate electrical connection.
  2. Connect the required power supply of 16–35 VDC or 19–28 VAC.
  3. Select the required CO₂ output: 4–20 mA, 0–5 VDC, or 0–10 VDC.
  4. Set the barometric pressure and perform field calibration if required for the installation.
  5. Verify the CO₂ and temperature readings at the connected controller or building automation system.
  6. Lock the push-button menu through the internal DIP switch when access protection is required.

Frequently Asked Questions

What does the Dwyer CDT-2N4E measure?

The CDT-2N4E measures CO₂ from 0 to 2000 PPM and temperature using a Pt1000 Ω RTD temperature output.

What CO₂ outputs are available?

The transmitter provides a universal CO₂ output selectable as 4–20 mA, 0–5 VDC, or 0–10 VDC.

What is the temperature range?

The temperature measurement range is 32 to 122°F (0 to 50°C).

How accurate is the CDT-2N4E?

CO₂ accuracy is ±40 ppm + 3% of reading, while temperature accuracy is ±1°C at 25°C.

What sensor technology does the CDT-2N4E use?

It uses a single-beam, dual-wavelength NDIR sensor with a stated 15-year life expectancy. The transmitter also provides digital barometric pressure adjustment and field calibration capability.

Does the CDT-2N4E have an integral display?

No. The CDT-2N4E does not have an integral LCD display. The CDT-2N4E-LCD is the corresponding configuration with an integral LCD.

Does the CDT-2N4E have a relay output?

No. The CDT-2N4E does not include a relay output.

What power supply does the CDT-2N4E require?

It operates from 16–35 VDC or 19–28 VAC and has an average power consumption of 2 W.

Where can the CDT-2N4E be used?

It is suitable for indoor applications including demand-controlled ventilation, schools, offices, hospitals, and LEED-driven ventilation monitoring.

Is genuine Dwyer stock available with UAE shipping?

Yes. General Tech Services LLC supplies genuine Dwyer Instruments products with free UAE-wide shipping. Call +971 6 5436933 for pricing and current availability.

Request a Quote Today

For pricing, availability, or technical assistance with the Dwyer CDT-2N4E CO₂/temperature transmitter, contact General Tech Services LLC.

Call: +971 6 5436933
Website: www.generaltechshop.ae

 

Availability: in stock
Free Kuwait shipping available
For pricing, please contact our experts.