Client Protection
Dedicated Support
Dwyer ISDP-002 | Differential Pressure Transmitter | 0 to 0.25 inH₂O, ± 0.5 %, 4 to 20 mA
The Dwyer ISDP-002 is a differential pressure transmitter: intrinsically safe differential pressure transmitter, range 0-0.25" w.c..
The Series ISDP Intrinsically Safe Differential Pressure Transmitter by Dwyer is designed for measuring differential pressure in air and non-corrosive gases within hazardous (classified) locations. The transmitter provides a robust solution for monitoring pressures or air flows where intrinsic safety certifications are required.Hazardous Locations: Class I Div 1 Groups A, B, C, D; Class II Div 1 Groups E, F, G; and Class III Div 1Zone Applications: Zone 0 (Ex ia IIC T4) The Series ISDP delivers ±0.5% accuracy at 77°F (25°C) including hysteresis and repeatability, following a one-hour warm-up.
- Accuracy: ± 0.5 %
- Accuracy Detail: ± 0.5% at 77°F (25°C) including hysteresis and repeatability (after 1 hour warm-up)
- Compensated Temperature, Max: 60 °C
- Compensated Temperature, Min: 0 °C
- Compliance Note: CE: CENELEC EN 61326/55024: 2003; IEC 61000-4-2/3/4/6: 2001/2006/2004/2005; CENELEC EN 55011: 2006; 2004/108/EC EMC Directive. FM Intrinsically Safe CLI Div I GR: A, B, C, D; CLII Div I GR: E, F, G; CLIII Div I.
- Damping Time: 1 s
- Specifications
- Features
- Downloads
| Part Number | ISDP-002 |
| Brand | Dwyer |
| Series | ISDP |
| Accuracy | ± 0.5 % |
| Accuracy Detail | ± 0.5% at 77°F (25°C) including hysteresis and repeatability (after 1 hour warm-up) |
| Compensated Temperature, Max | 60 °C |
| Compensated Temperature, Min | 0 °C |
| Compliance Note | CE: CENELEC EN 61326/55024: 2003; IEC 61000-4-2/3/4/6: 2001/2006/2004/2005; CENELEC EN 55011: 2006; 2004/108/EC EMC Directive. FM Intrinsically Safe CLI Div I GR: A, B, C, D; CLII Div I GR: E, F, G; CLIII Div I. |
| Damping Time | 1 s |
| Display Note | 4 digit LCD 0.6" H |
| Display Type | LCD |
| Electrical Connection | M12 4 pin Female |
| Electrical Output | 4 to 20 mA |
| Enclosure Ratings | IP66, NEMA Type 4X |
| Long Term Stability | < ± 1%/year |
| Materials | Aluminum, Glass |
| Measurement Pressure Type | Differential |
| Measurement Pressure, Max | 0.25 inH₂O |
| Measurement Pressure, Min | 0 inH₂O |
| Mounting Note | Vertical |
| Number of Digits | 4 |
| Operating Temperature, Max | 60 °C |
| Operating Temperature, Min | 0 °C |
| Output Signal | Current |
| Process Connection Size | 1/8 in |
| Process Connection Type | NPT Female |
| Proof Pressure | Up to 2 psi |
| Response Time | 250 ms |
| Span Adjustment | Menu Option |
| Supply Power Type | DC |
| Supply Voltage | 10 to 35 Vdc |
| Thermal Effects | 0.036%/°C |
| Thermal Effects Note | 0.020%/°F (0.036/°C) from 77°F (25°C) |
| Weight | 1.19 kg |
| Zero Setting Adjustable Range | Accessible via menus |
| Country of Origin | United States |
- Accuracy: ± 0.5 %
- Accuracy Detail: ± 0.5% at 77°F (25°C) including hysteresis and repeatability (after 1 hour warm-up)
- Compensated Temperature, Max: 60 °C
- Compensated Temperature, Min: 0 °C
- Compliance Note: CE: CENELEC EN 61326/55024: 2003; IEC 61000-4-2/3/4/6: 2001/2006/2004/2005; CENELEC EN 55011: 2006; 2004/108/EC EMC Directive. FM Intrinsically Safe CLI Div I GR: A, B, C, D; CLII Div I GR: E, F, G; CLIII Div I.
Other models in this series
Click a row to open that product.
Related Products
Dwyer 629C-05-R5-P1-E5-S3 | Wet/Wet Differential Pressure Transmitter | 0 to 100 psi, ± 0.5 %, 0 to 5Vdc
Dwyer 629C-05-R5-P1-E5-S3 | Wet/Wet Differential Pressure Transmitter | 0 to 100 psi, ± 0.5 %, 0 to 5Vdc
Dwyer 629C-05-CH-P2-E5-S3 | Wet/Wet Differential Pressure Transmitter | 0 to 100 psi, ± 0.5 %, 0 to 5Vdc
Dwyer 629C-05-CH-P2-E5-S3 | Wet/Wet Differential Pressure Transmitter | 0 to 100 psi, ± 0.5 %, 0 to 5Vdc
Dwyer 629C-05-R1-P1-E5-S3 | Wet/Wet Differential Pressure Transmitter | 0 to 100 psi, ± 0.5 %, 0 to 5Vdc
Dwyer 629C-05-R1-P1-E5-S3 | Wet/Wet Differential Pressure Transmitter | 0 to 100 psi, ± 0.5 %, 0 to 5Vdc
Dwyer 629C-05-CH-P2-E5-S1 | Wet/Wet Differential Pressure Transmitter | 0 to 100 psi, ± 0.5 %, 4 to 20 mA
Dwyer 629C-05-CH-P2-E5-S1 | Wet/Wet Differential Pressure Transmitter | 0 to 100 psi, ± 0.5 %, 4 to 20 mA
Dwyer 629C-04-CH-P2-E5-S3 | Wet/Wet Differential Pressure Transmitter | 0 to 50 psi, ± 0.5 %, 0 to 5Vdc
Dwyer 629C-04-CH-P2-E5-S3 | Wet/Wet Differential Pressure Transmitter | 0 to 50 psi, ± 0.5 %, 0 to 5Vdc
Dwyer 629C-03-CH-P2-E5-S1 | Wet/Wet Differential Pressure Transmitter | 0 to 25 psi, ± 0.5 %, 4 to 20 mA
Dwyer 629C-03-CH-P2-E5-S1 | Wet/Wet Differential Pressure Transmitter | 0 to 25 psi, ± 0.5 %, 4 to 20 mA
Dwyer 629C-02-R6-P1-E5-S1 | Wet/Wet Differential Pressure Transmitter | 0 to 10 psi, ± 0.5 %, 4 to 20 mA
Dwyer 629C-02-R6-P1-E5-S1 | Wet/Wet Differential Pressure Transmitter | 0 to 10 psi, ± 0.5 %, 4 to 20 mA
Dwyer 629C-03-CH-P2-E5-S3 | Wet/Wet Differential Pressure Transmitter | 0 to 25 psi, ± 0.5 %, 0 to 5Vdc
Dwyer 629C-03-CH-P2-E5-S3 | Wet/Wet Differential Pressure Transmitter | 0 to 25 psi, ± 0.5 %, 0 to 5Vdc