Dwyer L4TOP | FLOTECT® Float Switch
The Dwyer L4TOP is a FLOTECT® float switch: float switch, brass, SPDT, (V=4, H=3).
The Dwyer Series L4 Flotect® Float Switch is a rugged, magnetically operated point level switch designed to automatically indicate tank levels. The series operates by using a free-swinging float that attracts a magnet within the solid metal switch body, actuating a snap switch via a simple lever arm without bellows, springs, or seals. Documented applications include direct pump control (starting or stopping pumps), automatic tank dump operations, level control, valve control, and triggering level alarm signals.
- Conduit Connection: 3/4 in NPT Female
- Deadband: 3/4 in (19 mm)
- Electrical Connection: Pigtail Leads
- Electrical Rating Note: UL, FM, ATEX and IECEx models: 10 A @ 125/250 VAC (V~). CSA models: 5 A @ 125/250 VAC (V~); 5 A res., 3 A ind. @ 30 VDC (V ). MV option: 1 A @ 125 VAC (V~); 1 A res., .5 A ind. @ 30 VDC (V ). MT option: 5 A @ 25/250 VAC (V~). [MT and MV option not UL, CSA, FM, ATEX or IECEx]
- Enclosure Ratings: Hazardous Location Rated
- Enclosure Ratings Note: Weatherproof and Explosion-proof. **Listed with UL and CSA for Class I, Groups C and D; Class II, Groups E, F, and G; ATEX 2813 II 2 G Ex db IIB T6 Gb -20°C≤Tamb≤73°C. -20°C≤Process Temp≤73°C. EU-Type Certificate No.: KEMA 03 ATEX 2383. ATEX Standards: EN 60079-0:2012+A11:2013. IECEx Certified: For Ex db IIB T6 Gb -20°C≤Tamb≤73°C. -20°C≤Process Temp≤73°C. IECEx Certificate of Conformity: IECEx DEK 11.0071. IECEx Standards: IEC 60079-0:2011; IEC 60079-1:2014.
Other models in this series
Click a row to open that product.
Highlighted values differ from the model you are viewing.