The Dwyer CDT-2D44 is a duct-mount carbon dioxide and temperature transmitter with a 0-2000 ppm CO₂ range, universal 4-20 mA, 0-5 VDC or 0-10 VDC CO₂ output and an analog temperature output. It is designed for indoor air monitoring, demand-controlled ventilation and HVAC applications requiring duct-mounted CO₂ and temperature measurement. Genuine stock at General Tech Services LLC, UAE, with free UAE-wide shipping. Request a quote in under a minute - call +971 6 5436933.

Part No. CDT-2D44

Product Overview

The Dwyer Instruments Series CDT Carbon Dioxide Transmitters accurately monitor CO₂ concentration and temperature in indoor environments to support ventilation control and energy-saving applications. The CDT-2D44 is a duct-mount model with a 0-2000 ppm CO₂ range and an analog temperature output.

A single-beam, dual-wavelength NDIR sensor automatically compensates for light-source aging effects in occupied and unoccupied buildings. The transmitter also provides digital barometric pressure adjustment and field calibration capability.

The CO₂ output is universal and can be configured for 4-20 mA, 0-5 VDC or 0-10 VDC to match the connected controller. Its NEMA 4X (IP66) housing is suitable for duct applications with air velocities up to 4000 FPM (20.32 m/s), while the backplate electrical connection simplifies installation.

Key Benefits

  • 0-2000 ppm CO₂ measurement with analog temperature output
  • Single-beam, dual-wavelength NDIR sensor with 15-year life expectancy
  • Universal CO₂ output: 4-20 mA, 0-5 VDC or 0-10 VDC
  • CO₂ and temperature measurement in one transmitter
  • NEMA 4X (IP66) duct-mount housing
  • Suitable for duct air velocities up to 4000 FPM (20.32 m/s)
  • Digital barometric pressure adjustment
  • Field calibration capability
  • Backplate electrical connection
  • Genuine Dwyer Instruments stock with free UAE-wide shipping

Who This Product Is Best For

  • HVAC systems requiring duct-mounted CO₂ and temperature monitoring
  • Demand-controlled ventilation in schools, offices and hospitals
  • Building automation and ventilation control systems
  • Projects requiring a universal 4-20 mA, 0-5 VDC or 0-10 VDC CO₂ output
  • Applications requiring an analog temperature output
  • LEED-driven ventilation monitoring applications
  • Duct systems requiring a rugged NEMA 4X (IP66) transmitter housing

How to Specify & Commission It

  1. Confirm the application requires a 0-2000 ppm duct-mounted CO₂ transmitter with an analog temperature output.
  2. Mount the CDT-2D44 in the duct according to the installation manual and verify the duct air velocity is within the 4000 FPM (20.32 m/s) limit.
  3. Wire the power supply and select the required CO₂ output: 4-20 mA, 0-5 VDC or 0-10 VDC.
  4. Connect the analog temperature output to the controller.
  5. Set the digital barometric pressure adjustment and perform field calibration if required.
  6. Verify the CO₂ and temperature readings at the connected controller before placing the system into service.

Frequently Asked Questions

What does the CDT-2D44 measure?
It measures CO₂ from 0-2000 ppm and temperature through an analog temperature output.

What CO₂ outputs are available?
The transmitter provides a universal selectable output of 4-20 mA, 0-5 VDC or 0-10 VDC.

How accurate is the CDT-2D44?
CO₂ accuracy is ±40 ppm + 3% of reading at 2000 ppm. Temperature accuracy is ±1°C at 25°C.

What sensor technology is used?
The CDT-2D44 uses a single-beam, dual-wavelength NDIR sensor with a 15-year life expectancy.

What type of temperature output does it use?
The CDT-2D44 provides an analog temperature output. The supplied specifications do not identify a specific thermistor or RTD type.

Is the CDT-2D44 wall or duct mounted?
The CDT-2D44 is a duct-mount transmitter with a NEMA 4X (IP66) housing.

What is the maximum duct air velocity?
The transmitter is suitable for duct air velocities up to 4000 FPM (20.32 m/s).

Does it support field calibration?
Yes. The CDT-2D44 provides field calibration capability and digital barometric pressure adjustment.

Is genuine stock available with UAE shipping?
Yes. Genuine Dwyer Instruments stock is available from General Tech Services LLC, UAE, with free UAE-wide shipping. Call +971 6 5436933 for pricing and current availability.

Request a Quote Today

For pricing or to place an order, contact General Tech Services LLC.

Call +971 6 5436933 | www.generaltechshop.ae

 

Availability: in stock
Free Kuwait shipping available
For pricing, please contact our experts.